UV-03.1
UV flame detector
The UV-03.1 ultraviolet flame detector detects arcs and fires with open flames.
It responds to the UV-C radiation in the range of 185 – 260 nm that is mainly contained in the edges of the flames and is perfect for open flames without smoke development.
The detector does not respond to sunlight, incandescent lamps, fluorescent tubes or flying sparks.
Incorrect triggering is possible with light sources that emit UV radiation.
These include halogen and mercury vapor lamps, lightning, arcs during welding work and the reflections from these radiation sources.
In addition, smoke, dust and water vapor as well as dirt on the UV pane absorb the ultraviolet radiation and impair the response of the detector.
The detector is equipped with a nano-coated special filter glass that has excellent oleophobic and hydrophobic properties. Dust and dirt also have a hard time settling on the viewing pane, which means that air purging is not necessary in many applications.
UV-03.1 – data and facts
| Operating voltage |
12…30VDC=
|
| Operating current two-wire technology |
< 50µA
|
| Spectral sensitivity |
185…235 nm
|
| Viewing angle (without / with ventilation) |
approx. 110° / 35°
|
| Protection class of the housing | IP65 |
| Temperature range |
-20…+60°C
|
| Dimensions (without / with ventilation) | 98 x 64 x35 mm / 54 mm |
| Weight (without / with ventilation) | 300 g / 350 g |
| Alarm pulse (without latching) | ca. 1 s |
| Reaction time / detection distance (set to 2cm gas flame from 3mm pipe, 30% Prop. 70% But.) End of line resistance (activated via BR4=ON) |
150 – 250 ms / 80cm RE 4,7 KΩ |
| Response delay (adjustable) | 2 s, 4 s, 6 s |
Options and special features
|
Integrated potential-free relay contact (photo MOS relay, 30VDC / 0.5A) for “alarm”,
Equipped with special glass that has excellent oil and dirt-repellent properties, so that air purging is often not necessary.
The UV-03.1 is optionally available with a test circuit UV-03.1.TE, please specify when ordering.
By applying 24VDC, a UV test lamp is switched on and the detector including the sensor is tested.
The UV-03.1 has three status LEDs for operation, test and alarm. The UV-03.1 is optionally available with an M12 connector UV-03.1.ST, please specify when ordering. |
These products might interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.