FU-01.1
Single range spark extinguishing system control
The FU-01.1 spark extinguishing system controls and monitors single-zone spark extinguishing systems for protection from machines, piping, and paint and powder coating cabins. The equipment includes two monitored signaling lines: one for the spark sensor, the other for monitoring the flow monitor. In addition the device has two monitored outputs for warning and extinguishing, as well as relay outputs for malfunction, alarm and system-off.
The detection of more sparks causes an automatic extinguishing time delay by a preset time span. With an overrun, the system is switched off and an alarm is started. DIP switches enable configuration for a wide spectrum of applications. Along with the control elements there is also an LED status display on the front plate. There is an error message or alarm both with water flow without extinguishing, as well as with extinguishing without water flow.
FU-01.1 – Data and facts
Operating voltage |
230V~ (115V~)
|
Operating current at 230V~ |
ca. 65mA
|
Dimensions |
230 x 185 x 120 mm
|
Relay outputs | |
Malfunction, potential-free changeover contact |
1x 30V=/0,5A
|
Alarm, potential-free changeover contact |
1x 30V=/0,5A
|
System off, potential-free changeover contact |
1x 30V=/0,5A
|
Signaling circuits L1/L2 | |
Short circuit range |
0Ω…120Ω
|
Alarm range |
180Ω…900Ω
|
Operating range |
1,5kΩ…7kΩ
|
Open circuit range |
> 10kΩ
|
Spark counter (number of sparks) |
1…11
|
Output warning | |
Operating current |
< 0,5A
|
Extinguisher output | |
Operating current |
1A
|
Extinguishing time |
3…25s
|
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.