UE-02
One-zone extinguishing control centers
The one-zone extinguishing system control UE-02 is used for control and monitoring of single-zone extinguishing systems. The device can be configured via jumper settings to a wide area of applications and can also be used for HRD extinguishing systems. It has three monitored signaling lines with memory: two independent and one for the monitoring circuit.
UE-02 is compatible both in two-wire and four-wire technology with all Brandtronik sensors and with a large number of third-party manufacturers. The control system has relay outputs for malfunction, alarm and system-off and two monitored outputs for warning and extinguishing. The control elements, along with an LED status display, are located on the front plate.
UE-02 – Data and Facts
Operating voltage |
230V~=
|
Operating current |
ca. 55mA
|
Dimensions |
230 x 185 x 120mm=
|
Relay outputs | |
Malfunction, potential-free changeover contact |
1x 30V=/0,5A
|
Alarm, potential-free changeover contact |
1x 30V=/0,5A
|
System off, potential-free changeover contact |
1x 30V=/0,5A
|
Signaling circuits L1, L2, L3 | |
Short circuit range |
0Ω…120Ω
|
Alarm range |
180Ω…900Ω
|
Operating range |
1,5kΩ…7kΩ
|
Open circuit range |
> 10kΩ
|
Reaction time |
4ms / 100ms
|
Output warning | |
Operating current |
< 1A
|
Extinguisher output | |
Operating current |
1A (2A für 2min.)
|
Extinguishing time L1/L2 |
30s / unbegrenzt
|
Extinguisher delay L1/L2 |
5s / 10s
|
Short circuit monitoring |
can be switched off as needed
|
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.