UE-01.24.1/SV-01.1
Monitoring unit
with voltage supply
UV-01 Included in the equipment are potential-free changeover for alarm and error messages and an internal monitoring for the operating voltage. An error message occurs at Vb < 18 VDC.
The monitoring unit is compatible in two-wire technology with all Brandtronik sensors and with a large number of third-party manufacturers. It has an LED display for operation, sensor malfunction, extinguishing output malfunction and alarm. The reset button for the reset of devices and sensors is on the front plate.
The device can be mounted on a rail using a base. The external power supply SV-01.1 has a wide input range to permit power supply over the range of 90 – 264 V~/24 VDC/ 230 mA.
UE-01.24.1/SV-01.1 – Data and Facts
Operation voltage |
18…30VDC
|
Operating current |
30mA
|
Line monitored | |
Short circuit range |
0…120Ω
|
Alarm range |
180…900Ω
|
Operating range |
1,5…7kΩ
|
Open circuit range |
> 10kΩ
|
Temperature range |
-25…+60°C
|
Dimensions | |
with plugs |
22,6x105x69,5 mm
|
Potential-free changeover contact | |
Malfunction |
30VDC / 0,5A
|
Alarm |
30VDC / 0,5A
|
Voltage supply SV-01.S | |
Input voltage |
90…264V~
|
Output voltage |
24VDC ±2%
|
Output current |
< 230mA
|
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.