UE-01.24.1/SV-01.1
Monitoring unit
with voltage supply
The UE-01.24.1/SV-01.1 monitoring device is used for the simple monitoring of machines and system components.
The device has a monitored signaling circuit and a monitored trigger circuit for the extinguishing agents.
The equipment includes unmonitored potential-free changeover contacts for alarm and fault messages as well as internal monitoring for the operating voltage. The fault message is issued when Ub < 18 VDC.
The monitoring device is compatible with all BRANDTRONIK detectors and a large number of third-party products using two-wire technology.
It has an LED display for operation, detector fault, extinguishing output fault and alarm.
The reset button for resetting the device and detector is located on the front panel.
The device can be mounted on a rail using a base.
The external power supply SV-01.1 enables power supply in the range 90 – 264 VAC/ 230 mA via a wide-range input..
UE-01.24.1/SV-01.1 – data and facts
Monitoring device UE-01.24.1
| Operating voltage |
18…30 VDC
|
| Operating current Alarm current without consumer |
30 mA
60 mA |
| Detector line Short circuit area Alarm area Operating area Interruption area Line voltage |
1x monitored 0…120 Ω 180…900 Ω 1,5…7 kΩ > 10 kΩ 24 VDC |
| Output trigger Short circuit range Operating range Interruption range Monitoring current Operating current Extinguishing delay Standard Optional (please specify when ordering) |
1x monitored 0…15 Ω 25 Ω…1 kΩ > 2,5 kΩ 5 mA < 0,5 A permanently set without delay 5 s |
| Protection class of the housing | IP20 |
| Temperature range | -25…+60° C |
| Operating voltage monitoring fault | @Ub < 18 V |
| Dimensions Housing Base |
Housing / base 39 x 39 x 72 (high) mm 70 x 39 x 26 (high) mm |
| Assembly Housing Base |
attachable Housing attachable to base Standard rail DIN 46277 |
| Weight with base | 120 g |
| Potential-free relay outputs Fault Alarm Not “monitored” means it is not a “primary line” and therefore the line is not checked for “open circuit” and “short circuit”. |
2x_not_monitored
Terminals 4/5/6 Terminals 2/3 each
30 VDC / 0,5 A
|
Power supply SV-01.1
| Input voltage |
90…264 VAC
|
| Output voltage |
24 VDC ±2%
|
| Output current | < 230 mA |
| Protection class of the housing | IP20 |
| Temperature range | -25…+70° C |
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.