IR-01.1.ex / IR-01.1.S.ex
Infrared spark detector
The infrared spark detector IR-01.1.ex / IR-01.1.S.ex with a pressure-tight encapsulated housing detects sparks and flames in closed, explosion-hazardous systems. The maximum of its spectral sensitivity is around 850 nm (IR-01.1.ex) or around 980 nm (IR-01.1.S.ex). The device is well suited for sparks and flames with temperatures > 800°C.
It is designed for installation in parts of the system where it is completely dark and where no extraneous light is to be expected.
Detection distance IR-01.1.ex = 500 mm
Detection distance IR-01.1.S.ex = 1000 nm
Daylight contains infrared components that trigger the device and can therefore cause false alarms. IR-01.1.ex / IR-01.1.S.ex is used, for example, in electronic spark extinguishing systems with monitoring devices for the early detection of fires or explosions and wherever flammable or smoldering materials are transported mechanically or pneumatically and there is a risk of fire or explosion.
IR-01.1.ex – data and facts
| Operating voltage (without / with alarm relay) | 12…30 VDC / 18…30 VDC |
| Operating current @24V (without / with alarm relay) | < 200 µA / 5 mA |
| Spectral sensitivity | ca. 700…1000 nm |
| maximum detection distance
IR-01.1.ex |
@ Spark temperature 800°C
500 mm |
| Viewing angle | approx. 75° |
| Protection class of the housing | IP66 |
| Temperature range | -20…+70° C |
| Dimensions | Ø: 40mm, L=127 mm |
| End of line resistance
standard |
RE
not active |
| Alarm pulse | 0,3 s |
| Response delay (without / with alarm relay) | <1 ms / 1,5 ms |
| Weight (without / with 10m cable) | 850 g / 2600 g |
| Alarm current
without alarm relay (stamdard) |
@ Ub = 24 VDC 40 mA |
Options and special features
|
with optional potential-free contact for an alarm relay
A “fault relay” cannot be installed in this detector The detector is certified according to ATEX “Flameproof enclosure / Protection by housing” for Zone 1 / Zone 21: II 2G Ex d II C t6 Gb / II 2D Ex tb IIIC T80°C Db |
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR