IR-01.1 / IR-01.1.S
IR spark detector
The infrared spark detector IR-01.1 / IR-01.1.S detects sparks and flames in closed systems. The maximum of its spectral sensitivity is around 850 nm (IR-01.1) or around 980 nm (IR-01.1.S).
The device is well suited for sparks and flames with temperatures > 800°C. It is designed for installation in parts of the system where it is completely dark and where no extraneous light is to be expected.
Detection distance IR-01.1: 500 mm
Detection distance IR-01.1.S: 1000 mm
Daylight contains infrared components that trigger the device and can therefore cause false alarms. IR-01.1 / IR-01.1.S is used, for example, in electronic spark extinguishing systems with monitoring devices for the early detection of fires or explosions and wherever flammable or smoldering materials are transported mechanically or pneumatically and there is a risk of fire or explosion.
The detector is equipped with a nano-coated special filter glass that has excellent oleophobic and hydrophobic properties. Dust and dirt also have a very hard time settling on the viewing window, which means that air purging is not necessary in many applications.
IR-01,1 – data and facts
| Operating voltage (without / with alarm relay) | 12…30 VDC / 18…30 VDC |
| Operating current at 24V (without / with alarm relay) | < 200 µA / 5 mA |
| Spectral sensitivity | approx. 700…1000 nm |
| maximum detection distance IR-01.1 IR-01.1.S |
@ Spark temperature 800° C 500 mm 1000 mm |
| Viewing angle (without / with ventilation) | ca. 110° / 35° |
| Protection class of the housing | IP65 |
| Temperature range | -20…+70° C |
| Dimensions
without ventilation |
Diameter, length
Ø: 40mm, L=76 mm |
| internal resistors
Alarm resistor |
configurable according to customer requirements
560 Ohm |
| Response delay (without / with relay) | < 1 ms / 1,5 ms |
| Alarm pulse | 0,3 s |
| Weight (without / with ventilation) | 180 g / 210 g |
| Fault message @JU1 = ON |
Ub < 16,5 VDC
|
Options and special features
|
with terminal box (standard) IR-01.1(.S) Optional without terminal box, with connection cable IR-01.1(.S).KA Optional without terminal box with M12 connector IR-01.1(.S).ST Optional with air flow IR-01.1(.S).LU Optionally with potential-free contacts (relays) for “fault” and “alarm”
The fault relay is always a normally open relay, is operated inversely (fail-safe) and is activated with JU1=ON, which simultaneously activates the internal line end resistor. |
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.