IR-04
Infrared flame detector
with visibility monitoring
The IR-04 infrared flame detector with visibility monitoring detects open flames and fires in both organic and inorganic materials and is well suited for detecting flames with a temperature > 800°C.
The maximum of its spectral sensitivity is around 950 nm.
The ATEX-certified device (II 2D Ex tb IIIC T90° Db IP65 X -20 =< ta =< +70°C, Zone 21) is suitable for monitoring objects that are particularly at risk of fire and explosion.
Such as paint booths, powder spray booths, hardening plants, spark erosion machines, mechanical processing centers and dust extraction systems in which high levels of dust are to be expected and where visibility monitoring of the flame detectors is required.
The detector can be adapted to different ambient radiation (brightness, lighting) by setting different fire levels.
IR-04 – data and facts
Operating voltage |
15…30 VDC
|
Operating current |
< 35 mA
|
Spectral sensitivity |
ca. 780…1100 nm=
|
Viewing angle |
ca. 90°
|
Temperature range |
-20…+70° C
|
Dimensions Base housing Flange housing bottom Flange housing top |
Housing 98 x 64 x 36 mm ∅= 60 mm, h= 39 mm ∅= 48 mm, h= 27 mm |
Weight | 510 g |
Sensitivity Fire level 1 Fire level 2 Fire level 3 Fire level 4 |
Detection distance / flame area 6 m / 45 cm² 6 m / 660 cm² 6 m / 2600 cm² 6 m / 6000 cm² |
Fire level BS1 BS2 – BS3 – BS4 |
Environment, brightness, lighting Environment completely dark Environment dimly lit, no daylight Environment with daylight, without direct sunlight Environment with direct sunlight, glass facades |
Power-on suppression | approx. 10 s |
End resistance line output four-wire system (standard, adjustable) activated via JU5=ON, with end detector |
3,3 KΩ |
Alarm resistance line output four-wire system (standard, customizable) |
680 Ω |
Duration of alarm output in case of alarm, JU3 = OFF | Fire duration |
Response time, JU1+JU2 OFF / ON | 1 ms / 10 ms |
Protection class of the housing | IP 65 |
Material Base housing Detector housing and flange tube |
Housing Aluminium – die-cast Aluminium – anodised |
Options and special features
Integrated visibility monitoring with fault reporting
Internal monitoring of the operating voltage, fault at Ub < 15.0VDC
ATEX approval according to EU Directive 2014/34/EU
II 2D Ex tb IIIC T90° Db IP65 X -20 =< ta =< +70°C
Detector configuration
- line detector / end detector, please specify when ordering
(Standard: end detector -> line end resistance is active) - In case of a fault (no alarm / alarm) possible, please specify when ordering
(Standard: In case of a fault, an alarm is possible).
The detector is optionally available with an M12 connector (without ATEX certificate) IR-04.ST
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.