UV-01.1.ex
Ultraviolet flame detector
The UV-01.ex ultraviolet flame detector with pressure-tight encapsulated
metal housing detects fires with open flame as well as arcs in potentially explosive areas. It responds to the UV-C radiation mainly contained in the flame borders, in the range from 185 to 235 nm, and is very well suited for open flames without smoke development.
The sensor does not respond to sunlight, light bulbs, fluorescent lights or
flying sparks. False tripping is possible, however, with UV radiating light sources. Included in this are, for example, halogen and mercury vapor lamps, lightning, arc during welding work and reflections of the above radiation sources. In addition, smoke, dust and water vapor, as well as contamination of the UV pane, absorb the ultraviolet radiation and therefore negatively effect the response behavior of the sensor.
UV-01.ex – Data and Facts
Operating voltage |
15…30VDC=
|
Operating current at 24V |
< 120µA
|
Spectral sensitivity |
185…260 nm
|
Viewing angle without ventilation |
ca. 75°
|
Temperature range |
-20…+70°C
|
Dimensions | |
Ø: 42mm, L=127mm
|
|
Sensitivity | |
(set to 2 cm gas flame from 3 mm tube, 30%prop.70%but.) |
100 – 200 ms/80cm
|
Options and special features
potentialfree relay contakt, opener / turn key, Photo-MOS-Relay UV-03.Rx |
These products might interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.