FU-01
Single range spark
extinguishing system control
The FU-01 single-zone spark extinguishing control is used to control and monitor single-zone spark extinguishing systems to protect machines, pipelines, painting and powder coating booths.
The equipment includes two monitored reporting lines: one for the spark detectors, the other for equipment monitoring.
The device also has two monitored outputs for warning and extinguishing as well as unmonitored relay outputs for fault, alarm and production plant shutdown.
The detection of further sparks results in an automatic extension of the extinguishing time by a previously set period of time.
If an overflow occurs, the production system is switched off and an alarm is triggered.
DIP switches enable configuration for a wide range of applications.
In addition to the operating elements, there is also an LED status display on the front panel
FU-01 – data and facts
| Operating voltage (standard) adjustable at the factory |
230 VAC
115 VAC
|
| Operating current at 230 VAC (with “fault” and buzzer) |
approx. 65 mA
|
| Relay outputs Fault Alarm Production plant offNot “monitored” means it is not a “primary line” and therefore the line is not checked for “open” and “short circuit”. |
3x not monitored
Terminals 24 / 26 Terminals 21 / 23 Terminals 27 – 29 each with a potential-free changeover contact
30 VDC / 0.5
|
| Detection lines L1 for spark detectors L2 for extinguishing agents Short circuit area Alarm area Operating area Interruption area Line voltage |
2x monitored
Terminals 6, / 7 Terminals 9 / 10 0Ω…120Ω 180Ω…900Ω 1.5kΩ…7kΩ > 10 KΩ 27 VDC |
| Spark counter (number of sparks, adjustable) |
2, 4, 6, 8, 10
|
tr>
| Output Warning Short circuit range Operating range Interruption range Monitoring current |
1x monitored
Terminals 15 / 16 0….22 Ω 25…1.5 KΩ > 2.5 KΩ 5 mA |
| Battery internal external |
Terminals 4 / 5
max. 2×12 V / 0.8 Ah max. 2×12 V / 10 Ah |
| Alarm delay (detector to extinguishing control) | 4 ms |
| Extinguishing time (adjustable) |
3…25 s
|
| Temperature range | 0° C to 40° C |
| Protection class housing | IP 65 |
| Dimensions | 230 x 185 x 120 mm |
| Weight without battery with battery |
without/with battery 1.6 kg 2.3 kg |
special features
– Switchable time limit of 210 s for the warning.
– Internal and external option to switch off the extinguishing trigger.
– A test button for triggering can be integrated into the front panel if required.
– Functions such as alarm, warning and production shutdown are possible by setting the bridges using DIP switches.
– After each extinguishing, the control panel is immediately ready for another extinguishing; during an active extinguishing, a new spark extends the extinguishing time by the set time.
– Integrated adjustable spark counter, in the event of an overflow -> alarm and shutdown of the system.
– External connection for switching off the system.
– Delay in the fault message in the event of a power failure approx. 12s.
– Delay in the fault message in the event of a battery failure approx. 100s.
– Status display of the control panel via LED on the front panel.
– Control elements on the front panel:
Revision switch
Confirmation button Buzzer
Reset button
Attention!!
If an alarm is triggered and the production plant is shut down, the cause must be investigated.
These products might be interesting for you
UV-
FALME DETECTOR
Ultraviolet flame detectors detect both open flame and arc fires and are particularly suitable for use in potentially explosive atmospheres.
IR-
FALME DETECTOR
The infrared flame detector detects open flames and fires of both organic and inorganic materials and is well suited to flame detection.
UV-
SPARK DETECTOR
The infrared spark detector detects sparks and flames in closed systems, such as absolutely dark system parts with very little extraneous light incidence.
IR/UV-COMBI-FLAME DETECTOR
The IR/UV combination flame detector detects fires with an open flame involving carbon. This is well suited for open flames without smoke development.