UV-01.1
UV flame detector
The UV-01.1 ultraviolet flame detector detects both open flame fires and arcs.
It responds to the UV-C radiation in the range of 185…260 nm, which is mainly contained in the edges of the flames,
and is very suitable for open flames without smoke development.
The device is available with and without ventilation.
The detector does not respond to sunlight, incandescent lamps, fluorescent tubes and flying sparks.
False triggering is possible, however, with light sources that emit UV radiation. These include, for example, halogen and mercury vapor lamps, lightning, arcs during welding work and the reflections of these radiation sources.
Smoke, dust and water vapor as well as dirt on the UV pane also absorb the ultraviolet radiation and impair the detector’s response.
Caution!
Do not place window glass in front of the detector. The detector cannot detect fire through window glass.
Caution!
Only clean the viewing pane with a damp cloth, risk of static charge! -> False triggering
UV-01.1 – data and facts
| Operating voltage |
15…30 VDC=
|
| operating current two-wire technology |
< 70 µA
|
| Spectral sensitivity |
185…260 nm
|
| Viewing angle (without / with airflow) |
ca. 110° / 35°
|
| Protection class of the housing | IP65 |
| Temperature range |
-20…+70° C
|
| Reaction time/detection distance (set to 2cm gas flame from 3mm pipe, 30%Prop. 70%But.) |
100 – 200 ms/80 cm
|
| Dimensions without ventilation (without / with plug) with ventilation (without / with plug) |
Ø=40 mm l=77 / 91 mm l=95 / 109 mm |
| Weight (without / with airflow) | 110 g / 140 g |
| Alarm pulse | ca. 1 s |
| internal resistors, according to customer requirements Alarm resistor End of line resistor (activated by JU1=ON) |
configurable |
Options and special features
|
Optional:
Equipped with special glass that has excellent oil and dirt-repellent properties, so that air flushing is often not necessary |