Infrared-Ultraviolet Combined Flame Detection Unit
This detection unit is equipped with one infrared and one ultraviolet detector. This unit will signal alarm only upon response of both detectors. It is particularly safe against false alarm as detectors operate on individual wave bands. DIP switches provide setting options for varying levels of sensitivity and response times of each detector, enabling configuration of different alarm triggering combinations.
Key data:
Ingress protection IP65
Two-line Detection system
Operating voltage and current 24 VDC < 120 µA
Alarm resistor 560 Ω Standard
Response time min. 5 or 10 s.
Housing dimensions 125 x 80 x 58 mm
IU-01
Infrared-Ultraviolet Combined Flame Detection Unit 12 to 24 VDC
Price upon request.
IU-01.LU
Infrared-Ultraviolet Combined Flame Detection Unit with ventilation 12 to 24 VDC