This Detector detects sparks and flames in closed systems.
In its function this Detector is identical with IR13; equipped with one optical fibre.
Key data:
Ingress protection IP65
Two-line and four-line Detector systems
One optical fibre, 1m (different lengths available)
Operating voltage and current 24 VDC < 100 µA
Alarm resistor 560 Ω and 10 kΩ standard
Relay outputs for alarm and fault
Housing dimensions 125 x 80 x 58 mm
IL-11
IR Spark Detector
Price upon request.
IR-13
IR-13
Infrared Spark Detector
This Detector detects sparks and flames in closed systems. It is equipped with three optical fibres as Detector leads, usable in ambiental temperatures of up to 250° C. Special optical fibre models for temperatures of up to 700° C are available.
This Detector also features a potential-free toggle for fault and alarm.
Key data:
Ingress protection IP65
Two-line and four-line Detector systems
Three optical fibres, 1 m, (different lengths available) Operating voltage and current 24 VDC < 100 µA
Alarm resistor as per system 560 Ω and 10 kΩ
Housing dimensions 125 x 80 x 57 mm
IR-13
Infrared Spark Detector, ATEX 3G, 1/2D
Price upon request.
IR-13.EX
Infrared Spark Detector, ATEX 1/3G, 1/2D
Price upon request.
Three optical fibres as EX model
IR-23
IR-23
Infrared Spark Detector
This Detector is identical with IR13 above as regards function. Equipped with three optical fibres as Detector leads, usable in ambiental temperatures of up to 250° C. Special optical fibre models for temperatures of up to 700° C are available. This Detector features a checking device to monitor function and contamination of optical fibres.
Key data:
Ingress protection IP65
Two-line and four-line Detector systems
Three optical fibres, 1m, (different lengths available)
Operating voltage and current 24 VDC < 100 µA
Alarm resistor as per system 560 Ω and 10 kΩ
Housing dimensions 160 x 100 x 82 mm